|
Content
- Common aspects
- Stand-alone system
- Parallel use of wind- and diesel-generators
- Grid-parallel system
The market for wind-diesel systems is found in regions, where it would
be expensive to supply bigger power-plants with fuel and/or the public
grid is not available or not stable enough or the electrification is not
yet realized.
The use of diesel-generators together with a wind turbine is based on
the need of storage elements for energy in autonomous systems. Bad expierience
with battery/inverter-systems lead back to the use of the conventional
diesel technology because this is more economical. In a well set up installation
the diesel-engine is only used as a backup for the wind turbine. The first
priority is: use as little diesel fuel as possible.
The main technical problems in our development work which needed a lot
of practical expierience to be solved were situated in a high-reliability
regulation of the wind turbine without being led by a stable electric grid
and in the system management using the Diesel engines.
The construction of a larger electric network is possible with such
a system by just adding new energy supply units.
1.
Common aspects
The
Wuseltronik system is based on a number of autonomous energy supply units
with their own controls. Each module runs independently of other generators.
It can be used for stand-alone systems, weak electrical networks or a national
grid with the quality of the North-European network. A failure of one unit
does not influence the function of the others.
The basic concept of this control (in the simplest case only one diesel-generator
or wind turbine in stand-alone mode) was designed to give the possibilty
of adding new energy supply units if more power is used or a higher reliability
is necessary. Step by step a stand-alone system can be supplemented to
a wind-diesel system and combined with other small systems to a regional
electrical network or be connected to the national grid.
One essential quality is to dispense with a central system management.
In other systems a central computer controls each energy supply unit, collecting
measurement data about the electric power and generating on/off commands
for each unit. In the concept of Wuseltronik the autonomous control units
get all information necessary for running the system throughout the frequency
of the common grid.
Depending on varying conditions for the operation of an energy system
there are different possibilities for managing an energy supply unit. The
customer is able to program different preset-values for system management
by using simple commands on a small keyboard. In this way a modification
and optimization of settings within a wide range is easily done.

2.
Stand-alone system
In this system there is only one energy supply unit (i.e. wind energy
converter) running and feeding the electrical network. There is no connection
to other supply units (i.e. diesel generator) or to the public mains.
The rotation speed of the wind turbine which is proportional to the
frequency of the grid is kept constant. Measurement of the revolutions-per-minute
is done by counting the frequency of the grid. If a preset-value for the
frequency is exceeded (i.e. by high wind speed, gusts) an electrical dummy-load
is added by phase control to regulate the frequency to a stable value which
is programmed by the customer. The tolerance range is within some tenth
of a Hertz, thus any consuming device can be used in this supply system.
If an additional load is switched onto the grid at the same time the
same amount of electrical power in the dummy-load is reduced. It is not
possible to add a load which exceeds the actual regulated power because
otherwise the frequency of the system would decrease and the wind turbine
would have to be shut-down. The maximum power available in the system depends
on the actual wind energy input.
Therefore we give the user of a windpower stand-alone system the possibility
to define a number of different load-circuits which are programmed on the
keyboard. Each circuit has a fixed maximum power and a connection to the
grid is only possible when the actual power available exceeds the sum of
the required power.
If the frequency (revolutions per minute) falls short of a programmable
value the generator is separated from the grid. A reconnection is possible
if the wind turbine exceeds its nominal revolutions-per-minute again and
is able to deliver a defined quantity of electrical power.

3.
Parallel use of wind- and diesel-generators
This configuration is able to deliver an autonomous grid for all possible
situations of loads and available windpower. There is no connection to
the public grid. The information about the balance of power necessary for
the decision if a diesel engine is started can be taken out of one measurement
value which is available to each energy supply unit: the frequency of the
grid. Therefore we call a system like this ´frequency managed´,
that means the frequency of the grid varies depending on it´s actual
condition in balance of power in a range of typically *2% of it´s
nominal value (50 Hz). If the frequency is higher than the nominal value
only the wind turbine is connected to the grid. With a decreasing frequency
the energy which can be taken from the wind turbine also decreases and
the diesel-engine/s must be started to stabilize the grid.
Concerning the system-management each energy supply unit needs to have
a power/frequency-characteristics as shown in figure 2. The wind turbine
is stall-regulated with the rotor blades at a fixed angle to the axis.
Because of the highest priority given to the use of wind energy in the
wind-diesel system the control characteristics for the wind turbine are
the same as in a stand-alone system. If a higher power than actually available
is demanded, the frequency decreases and the diesel starts working. It´s
preset-value for the nominal frequency is slightly beyond the nominal value
of the wind turbine. Because of this small difference in the characteristics
a certain amount of power flows back into the diesel engine/s until they
cut off at a preset-value of reverse power if the demanded power is reduced
or the wind energy input rises. The wind turbine then works on it´s
own.
Depending upon the demanded availability of the grid other variations
of power management are possible. With the ´fuel-save´-mode
for instance the diesel keeps running independently of the actually required
power and the wind turbine only reduces the fuel-input. This mode is used
if a high base-load is connected to the grid. With anoter mode the diesel
is only started if a certain load is exceeded.

4.
Grid-parallel system
In this configuration the wind turbine or the wind-diesel system is
connected to another electrical network, i.e. the public grid.
The regulation of the wind turbine with dummy-loads is only necessary
at the moment of synchronization to the grid because the programmed nominal
value is higher than the maximum frequency of the grid.
All the power generated with the wind energy converter is fed into the
grid which may be considered as an infinite load breaking the wind turbine
exactly at grid-frequency. If the wind energy input is lowered down to
zero the generator is driven by the grid like a motor. Therefore the wind
turbine is disconnected by the control electronics beyond a programmable
amount of reverse power.
The diesel engine also works independently of the number/power of generators/loads
giving or taking electrical energy at the moment when it is used in parallel
connection to the public mains. For economical reasons the thermal losses
of an engine running parallel to the public network is commonly used in
addition to conventional oil or gas heating (combined heat and power).
The conditions for controlling the diesel are given by the thermal energy
flow in this special case. If the preset-value for the frequency is set
higher than the maximum frequency of the grid the diesel engine always
runs full power.A regulation to a required amount of thermal power is also
possible.
In the case of grid-failure the controls are able to automatically change
their mode to a stand-alone system. The diesel then works with a speed-regulation
at partial load depending on the balance of electrical power. It will rescue
a partial grid (in parallel to the wind turbine if possible) and regulate
it´s frequency to the preset-value with the above mentioned frequency/power-characteristics.
4.1. Wind turbine parallel to the public mains
Wind energy converters for use in stand-alone systems normally are regulated
to a fixed value of voltage. The controls work as follows:
If the voltage of the grid is lowered by an additional load, the controller
increases the induction current of the electrical generator to stabilize
the voltage again. If the load decreases the magnetic field is also decreased.
If two or more units run parallel, the current-flow (as a vector) in
each generator must be taken into consideration because the voltage of
the grid is now regulated by more than one controlling system. This performance
of the electronic controls is called ´statics´. A setting of
the statics-value causes a lower nominal voltage on inductive loads. Therefore
two parallel generators also deliver a certain amount of reactive power.
In a grid-parallel system this performance can no longer be used because
small changes in the voltage of the grid would desturb the controller.
Therefore an additional regulation of the phase-angle between voltage and
current in the generator (cos phi) is necessary.
In November 1993 the first wind energy converter with stand-alone and
grid-parallel operation, a ´Südwind N/E 1230´ (30 kW)
was connected to the electrical system and put into operation in Emden/Northern
Germany. Since early 1993 the synchronous generators of the wind turbine
and the parallel natural-gas-fired combined heat and power unit have been
running with good results. This was the first application for a wind turbine
with the possibility of use in a grid-parallel or autonomous system and
the whole range in between ´weak´ and ´hard´ networks.
Up to then the use of synchronous generators in small wind turbines
(up to 100 kW) had not been carried out worldwide. There is no technical
literature available on this particular application. Within the context
of a rising importance of an interconnection between small autonomous power
supply systems up to large regional networks in many countries the world
over, the results of this wind-diesel system carries particular weight.

|